5.Voltage manually calibration
Specification:
Rated voltage: 220V; Frequency: 50Hz/60HZ
Over current protection: 40A/63A (adjustable)
Under-voltage action switch-off value: 210V-145V (adjustable)
Over-voltage action switch-off value: 230V-300V (adjustable)
Reconnect time (delay on time): 1s-300s (default: 5s)
Error in real-time current, voltage : ≤2%
Setting method:
1.Press and hold the “SET” button for 3 seconds to enter the
parameter setting state.
1.1 When “Over(V) LED On,It means Setting the Over voltage
Value state,Press “UP” and “Down” can adjust the Over Voltage
value. default value is 270V
1.2 Press “SET” When “Under(V) LED on,It means Setting the
Under Voltage value state,Press “UP” and “Down” can adjust the
Over Voltage value. default value is 170V
1.3 Press “SET” When “Current (A) LED on,It means Setting the
Limit current value state,Press “UP” and “Down” can adjust the
Limit cureent value. Default Value is 40A.
2.When All data are set already,wait 40sec,then connect the
power.
3. Press “UP” and “Dwon”,reset the to default value.